Intumescent fire retardant coating | KF-FR100 | Kexin New Materials

Fire-resistive / intumescent coatings series · Complete application process flow

Product No.: KF-FR100 Standard: GB 14907 | GB 28375 | GB 12441 | GA 98 Version: V2.0 Date: 2026-06-21
I. Pre-application preparation — Substrate inspection and treatment

1Substrate inspection and preparation standard

Preparation standard:Abrasive-blast steel to grade Sa2.0–2.5 (ISO 8501-1)

Roughness requirement:per product requirements

Cleanliness requirement:Oil-free、No corrosion

Primer application:必须先Coating Application相容的Rust-ProofPrimer

2Paint preparation and mixing

Mixing method:Stir thoroughly with a power agitator until uniform and free of sediment.

Pot life:2K/Two-Component需在规定Time内用完

Thinning:Add a small amount of clean water (waterborne) or the dedicated thinner (solventborne) as required.

3Environmental condition check

Application temperature:5-35°C

Relative humidity:Relative humidity ≤85%

drying:Apply the next coat only after each coat has dried through.

II. Application procedure — Selection of coating method
Application methodProcess parametersApplicable scenarios
trowel application — 厚涂型Steel structure fire-retardant coating
Spraying Funnel-feed (hopper) spray gun, pressure 0.4–0.6 MPa Large-area application
Roller Coating — 薄涂型/Decorative-type fire protection涂料

Film ThicknessControl:Apply in multiple coats, each coat built up to the thickness required by the product. Thick-film type: ≤ 8 mm per coat; thin-film type: ≤ 0.5 mm per coat. Build up to the design thickness.

4. Safety and environmental requirements
⚠ PPE required: dust mask + safety goggles + gloves + safety shoes
⚠ 高空作业系Safety带
⚠ Water-BasedProductsSecurity较好,Solvent type需Ventilation
5. Quality inspection and acceptance criteria
Inspection itemsInspection methodAcceptance criteria
Dry film thickness Coating thickness gauge Complies with design values,no negative tolerance
Bond strength Pull-off test ≥0.15MPa
Appearance Visual No cracking, hollowing or delamination
FireproofPerformance Fire-resistance ratingtest CompliesDesignFire-resistance rating(h)
Prepared on the basis of:GB 14907 | GB 28375 | GB 12441 | GA 98 and relevant industry standards.
Important statement:This construction guide is a recommended reference document. Actual construction parameters should be adjusted based on site conditions, environmental circumstances, and coating system requirements. For special working conditions or construction difficulties, please contact the Kexin New Materials Technical Department for professional support.
Technical support:0757-88793275 | www.psste.com | Shunde District, Foshan City, Guangdong Province